RTD Temperature Transmitter - 316 Stainless Steel Construction |
| TX94A-SS Series Temperature Transmitter |
|
 |
|
|
|
|
|
$
195.00
TX94A-1-SS-M12F-1
|
| |
Ideal for Wash-down, Outdoor, Sanitary or Marine Environments
|
| |
Compact Design Attaches Directly to Most 3-Wire and 4-Wire, Pt100, 0.00385 Curve Sanitary Probes and Sensors with M12 Style Connectors
|
| |
True 2-Wire Operation, Loop Powered 4 to 20 mA Output
|
| |
Sealed Signal Conditioner Built Into NEMA 4X (IP67) 316 Stainless Steel Housing
|
| |
±0.1% FS Accuracy, High Repeatability, and Stability
|
| |
Both Zero and Span Adjustments for Field Calibration
|
| |
Provides “Upscale” Break Detection and Compensates for Long Lead Wires
|
View related products - Sanitary
|
| |
|
|
|
 |
Loop Powered!
The OMEGA® 2-wire TX94A-SS
Series temperature transmitters are
high-performance, industrial
transmitters designed for direct
connection to most CIP (clean-inplace)
Sanitary Pt100 probes and
sensors that incorporate a M12 style
connection. All models feature a
miniature signal conditioner built into
a sealed stainless steel connector
housing. The signal conditioner
converts the resistive change of a
100 Ω, 0.00385 RTD probe or
sensor into an industry-standard
2-wire, 4 to 20 mA analog output
across a dedicated temperature
range. Output connection is also a
standard M12 connector.
| M12 RTD SENSOR WIRING |  |  | | Wiring option #1 | Wiring option #2 | The TX94A-SS transmitter is provided with two RTD wiring configurations as shown. The wiring style is identified at the end of the model number by either a "-1" or "-2". If used with an Omega PR-21 sensor, then the "-1" or "-2" selection should match the final charecters following the "-M12" in the sensor model number (ie: PR-21A-3-100-A-1/4-0600-M12-1). When using the transmitter with an Omega PR-22 style RTD, then please select the -2 wiring configuration. Examples:
For use with a PR-21A-3-100-A-1/4-0600-M12-1, use an TX94A-2-SS-M12F-1 Transmitter (Range is -18 to 93°C).
For use with a PR-22-3-100-A-M6-250-M12 sensor, use an TX94A-2-SS-M12F-2 Transmitter (Range is -18 to 93°C).
SPECIFICATIONS
Supply Voltage: 8 to 35 Vdc; (24 Vdc recommended)
Max Load: Rmax (Ω) = (Vsupply - 8V)/0.02 A
Output: Linearized 4 to 20 mA
Accuracy: ±0.1% FS (includes effects of linearity, hysteresis and repeatability)
Frequency Response: 3 dB @ 3Hz
Range:
1: -40 to 49°C (-40 to 120°F)
2: -18 to 93°C (0 to 200°F)
3: -18 to 149°C (0 to 300°F)
4: -18 to 260°C (0 to 500°F)
Input: 3-wire, Pt100 (α = 0.00385), 4-wire RTD compatible Probe/Sensor Input
Connection:
TX94A-SS-M12M: M12 style, 4-pin male
TX94A-SS-M12F: M12 style, 4-pin female
Transmitter Operating Temp: -40 to 85°C (-40 to 185°F)
Output Connection (All Models): M12 style (order cable from table below)
Housing: 316 stainless steel, polished mirror finish
Approvals: CE marked
Dimensions: 51 H x 38 mm D (2.0 x 1.50")
|
| |
 |
|
 |
|
 |
† All dollar amounts on this site are shown in US currency.
Note: The TX94A-SS series has not been designed for use in medical or nuclear applications, nor flammable or explosive environments.
Ordering Example: (1) TX94A-2-SS-M12F-2 4 to 20 mA output transmitter with -18 to 93°C (0 to 200°F) temperature range, M12 style 3-pin male connection, $195.00, plus (1) PSR-24L Power supply, $60.00, $195.00 + 60.00 = $255.00
|
|
 |
|
 |
|  |
 |
 |
 |
 |
 |
 |
 |
 |
 |