ac Voltage and Current Measurement Transducers |
| OM8 Series |
|
 |
|
|
ac Voltage and Current Measurement Transducers
 |
| Click for larger image. |
|
|
|
|
|
|
 |
The OM8 series transducers convert AC currents and voltages to dc process signals for direct
connection to data acquisition and recording systems. The OM8 employ average measurement
techniques in conditioning the ac signal. For measurement of currents
and voltages greater than listed, the OM8 are directly compatible with
OMEGA instrument transformers.
Specifications
Accuracy: 0.2% of Reading
Sustained Input Overrange: Voltage, 120% continuous, 150% for 5 seconds; Current, 200% continuous, 1000% for 5 seconds
Outputs: 0 to 1 mA dc into 10 Kohm 10 Vdc compliance; 4-20 mA into 750 ohm Max 15 Vdc compliance
Zero Adjust: ±5% minimum
Span Adjust: ±10% minimum
Response Time: <400 msec (0-99% of full scale)
Power Consumption: 5 VA max
Isolation:
Input to output: 2500 Vac, 60 Hz, 1 min;
Input to power: 2500 Vac, 60Hz, 1 min;
Input to case: 2500 Vac, 60 Hz, 1 min;
Power to Output: 2000 Vac, 60 Hz, 1 min;
Power to case: 2000 Vac, 60 Hz, 1 min;
Output to case: 500 Vac, 60 Hz, 1 min
Dimensions:
Self powered units: 104 H x 101 D x 51 mm D (4.1" x 4.0" x 2.0");
auxiliary powered units: 120 H x 133 W x 96 mm D (4.7" x 5.2" x 3.8")
ac Current (Average Measuring) Transducers
| Model No. | Input Signal | Input Frequency | Output Signal | Power Required |
| OM8-21382AFA0 | 0-5 Amp ac | 50/60 Hz | 0-1 mA dc | Self powered |
| OM8-21384AFA0 | 0-5 Amp ac | 400 Hz | 0-1 mA dc | Self powered |
| OM8-21382AHD1 | 0-5 Amp ac | 50/60 Hz | 4-20mA dc | 120 Vac |
| OM8-21384AHD1 | 0-5 Amp ac | 400 Hz | 4-20mA dc | 120 Vac |
| OM8-21382AHD2 | 0-5 Amp ac | 50/60 Hz | 4-20mA dc | 240 Vac |
| OM8-21384AHD2 | 0-5 Amp ac | 400 Hz | 4-20mA dc | 240 Vac |
ac Voltage (Average Measuring) Transducers
| Model No. | Input Signal | Input Frequency | Output Signal | Power Required |
| OM8-22332AFA0 | 0-150 Vac | 50/60 Hz | 0-1 mA dc | Self powered |
| OM8-22334AFA0 | 0-150 Vac | 400 Hz | 0-1 mA dc | Self powered |
| OM8-22332AHD1 | 0-150 Vac | 50/60 Hz | 4-20mA dc | 120 Vac |
| OM8-22334AHD1 | 0-150 Vac | 400 Hz | 4-20mA dc | 120 Vac |
| OM8-22332AHD2 | 0-150 Vac | 50/60 Hz | 4-20mA dc | 240 Vac |
| OM8-22334AHD2 | 0-150 Vac | 400 Hz | 4-20mA dc | 240 Vac |
| OM8-22362AFA0 | 0-300 Vac | 50/60 Hz | 0-1 mA dc | Self powered |
| OM8-22364AFA0 | 0-300 Vac | 400 Hz | 0-1 mA dc | Self powered |
| OM8-22362AHD1 | 0-300 Vac | 50/60 Hz | 4-20mA dc | 120 Vac |
| OM8-22364AHD1 | 0-300 Vac | 400 Hz | 4-20mA dc | 120 Vac |
| OM8-22362AHD2 | 0-300 Vac | 50/60 Hz | 4-20mA dc | 240 Vac |
| OM8-22364AHD2 | 0-300 Vac | 400 Hz | 4-20mA dc | 240 Vac |
|
| |
 |
|
 |
|
 |