Accessibility  Skip navigation  Site Map  Help  Search field  View shopping cart  View shopping cart  Skip to Navigation
Omega.com - Your One-Stop Source for Process, Measurement and Control! (888) TCOMEGA (in US/Canada) or (203) 359- 1660 (for international)
Navigation Image Map  
search
      
 

Toroidal Conductivity System

CDTX-45T   
Made in the USA
 
Toroidal Conductivity System
CDTX-45T:Toroidal Conductivity System
Click for larger image.
   
$ 725.00  CDTX-45T1
Loop-Powered, AC, or Battery Versions
Dual Alarm Relays/Analog Outputs
Large, 2-Line Display

View related products - Conductivity Instrumentation

Click to scroll below to order See Specs PDF Manuals View a printer friendly page

The CDTX-45T toroidal conductivity system is designed for online monitoring of chemically aggressive process solutions, water applications that coat or foul traditional sensors, and plating bath operations in which high current densities are present. The sensor consists of 2 metallic ribbon coils that are fixed in place by the sensor jacket material. The drive coil is used to induce a current in the process solution. The second sensing coil is used to measure the current in the process solution; the magnitude of this current is proportional to the conductivity of the process solution. Toroidal sensor is available in Noryl to ensure that sensor-wetted materials are chemically resistant to process chemicals. The sensor material is non-conductive, thereby isolating the sensor from electrical noise and ground loops that can influence the integrity of the measurement. This material also makes the sensor resistant to electrode coating, since most substances do not adhere to the sensor material. Sensor can be submersion mounted for easy installation in open tanks or pipe mounted in the optional 2" tee fitting, which is keyed to the sensor for proper alignment. Tee fitting material is polypropylene. For larger pipe diameters, the sensor can be insertion mounted through a 1 1/2 NPT ball valve for easy retraction. The CDTX-45TC is the concentration monitor. The monitor comes with concentration/temperature tables for sodium hydroxide, potassium hydroxide, hydrochloric acid, nitric acid, and sulfuric acid.

MONITOR PERFORMANCE SPECIFICATIONS
Measuring Range:
    Main Input: 0 µS to 2000 mS, mg/L total dissolved solids; loop current 4 to 20 mA
    Sensor Temperature: -10 to 210ºC (14 to 410ºF)
    Main Parameter Ranges: 0 to 2000 µS, 0 to 2 mS, 0 to 20 mS, 0 to 200 mS,
    0 to 2000 mS, 0 to 2 S
Repeatability: 0.3% of span or 0.1 µS, whichever is greater
Sensitivity: 0.05% of span or 0.1 µS, whichever is greater
Non-Linearity: 0.3% of span or 0.1 µS, whichever is greater
Stability: 0.1% of span per 24 hr
Temperature Drift: Span or zero, 0.03% of span/ºC
Warm-Up Time: 7 s to rated performance
Response Time: 6 s to 90% of step input at lowest setting Max Sensor-to-Analyzer Distance: 61 m (200')

SENSOR SPECIFICATIONS
Sensor: Toroidal electrode
Wetted Materials: Noryl
Sensor Cable: 6.1 m (20') standard, maximum length 61 m (200')
Response Time: 2 s to 90% FS
Temperature Range: 0 to 105°C (32 to 221°F)
Pressure Limit: 150 psig
Process Connection: 3/4 MNPT rear thread, optional 2" keyed tee fitting
Temperature Element: Pt1000 RTD
Minimum Conductivity: 500 µS

INSTRUMENT SPECIFICATIONS
Enclosure:
    Materials: NEMA 4X (IP66) polycarbonate, stainless steel hardware,
    weatherproof and corrosion resistant
    Dimensions: 112 H x 112 W x 89 mm D (4.4 x 4.4 x 3.5")
Mounting Options: Wall, panel (115 x 115 mm) or pipe/handrail
Conduit Openings: 3 M16 openings; cord grips and conduit adaptors included
Weight:
    Loop-Powered Transmitter: 0.45 kg (1 lb)
    Other Configurations: 0.68 kg (1.5 lb)
Display: Large, high-contrast, super-twist (STN) LCD 4-digit main display with sign, 19.1 mm (0.75") 7-segment characters; 12-digit alphanumeric second-line display, 7.6 mm (0.3") 5 x 7 dot matrix characters
Keypad: 4-key membrane type with tactile feedback, polycarbonate with UV coating, integral EMI/static shield and conductively coated window
Ambient Temperature:
    Operating: -20 to 60ºC (-4 to 140ºF)
    Storage: -30 to 70ºC (-22 to 158ºF)
Ambient Humidity: 0 to 95% RH, non-condensing
     Designed for hazardous and non-hazardous areas
EMI/RFI Influence: Designed to EN 61326-1
Output Isolation: 600 V galvanic isolation
Filter: Adjustable, 0 to 9.9 minutes additional damping to 90% step input
Temperature Input: Selectable Pt1000 or Pt100 RTD with automatic compensation
Please download specification page for complete list of available models.


To Order (Specify Model Number)    
expand listWhat Other People Bought: When you see this icon, click on it to expand a list of products that other people have bought when they purchased this model.
 Part Number   Availability   Price   Description    Qty.
 Conductivity Analyzer
Click to expand/minimize a list of what others bought with the CDTX-45T1  CDTX-45T1 In Stock   $725.00    Loop powered 16 to 35 Vdc, 2-wire (4 to 20 mA output)  
    CDTX-45T2 In Stock   $975.00    120 Vac, 2 relays, two 4 to 20 mA outputs  
    CDTX-45T3 2 Weeks   $975.00    230 Vac, 2 relays, two 4 to 20 mA outputs  
    CDTX-45T4 In Stock   $975.00    Battery operated (9 V), two 0 to 2.5 Vdc outputs  
    CDTX-45T5 8 Weeks   $1,375.00    Battery operated (9V), internal data logger  
 Concentration Analyzer
    CDTX-45TC1 In Stock   $725.00    24 Vdc, 2-wire (single output only)  
    CDTX-45TC2 In Stock   $975.00    120 Vdc, 2 relays  
    CDTX-45TC3 In Stock   $975.00    230 Vdc, 2 relays  
    CDTX-45TC4 8 Weeks   $975.00    Battery operated, two 0 to 2.5 Vdc outputs  
    CDTX-45TC5 8 Weeks   $1,375.00    Battery operated, internal data logger  
 Sensor with 20' Cable**
Click to expand/minimize a list of what others bought with the CDE-45T2  CDE-45T2 In Stock   $475.00    Noryl electrode  
 Accessories
    CDTX-45T-JB In Stock   $110.00    NEMA 4X (IP66) junction box  
    CDTX-45T-C(*) 8 Weeks   $2.00    Sensor-interconnect cable  
    CDTX-45T-PT In Stock   $106.00    2" keyed slip-fit flow cell for use with polypro sensors  
    CDTX-45T-SMK In Stock   $160.00    Submersible mounting kit for PEEK™ sensor  
    CDTX-45T-PMK In Stock   $45.00    Panel mount kit for analyzer  
All dollar amounts on this site are shown in US currency.

 Note: Comes complete with operator's manual.

** For extended cable lengths in foot increments up to 61 m (200'), add "-*" to model number, add $3/ft to price.

(OPTIONS SHOWN IN THIS "NOTE" ABOVE ARE PRICED IN US$)


 Ordering Example: (1) CDTX-45T2 conductivity analyzer, $975.00

 Related Links - Manual
 Product Manual
   Download  CDTX-45T Series - Toroidal Conductivity Monitor
   Download  CDE-45T - Toroidal Sensor
   
Keywords:Toroidal Conductivity System, current meters data acquisition equipment digital flow meter thermistor measurement

   Back to topBack to top

© Copyright 2003-2013  |  OMEGA ENGINEERING, Inc.
OMEGA
Privacy Statement  |  Terms and Conditions
   MXV MMV | 71
VerisignAmex, Visa, Mastercard
Skip to navigation


Home Quick Order Products Literature My Omega Omega Info Contact Us Cart Help Global