1/4 DIN Ramp/Soak Controller |
| CN2120 |
|
 |
|
|
|
|
|
|
|
| |
200 Segments
|
| |
90 Independent Programs
|
| |
9 Linked Programs
|
| |
11 Logic Inputs and 14 Digital Outputs
|
| |
Real Time Clock/ Calendar Option
|
| |
Universal Inputs (TC, RTD, Linear)
|
| |
Wide Range of Outputs: Relay, dc Pulse, ac SSR, or Analog
|
| |
Special Control Functions: Output Linearization and Split Outputs
|
| |
Output Failure Detection
|
| |
NEMA-4X (IP65) Face Plate
|
View related products - Temperature and Process Controllers and Power Switching Devices
|
| |
|
|
|
 |
The OMEGA® CN2120 Ramp/Soak Controller is a fully functional controller with flexibility to meet many demanding control applications. The controller has many standard and special features that allow precise programming for any profile application.
Program The 200 segments can be used in up to 90 programs. These programs can be linked together or run separately. For each of the programs, it is possible to: • Use up to 99 segments • Set program repetitions • At the end of program, either turn on an "end of program" digital output, turn off the control outputs, set the control output to a set value, or use the last set point of the program for control. • Set up to 14 events • Choose one of 5 PID groups/segment • Choose one of 10 Wait bands/segment
Real Time Clock Option: Allows for auto start program at specific time and on specific days.
Special Control Features The CN2120 provides special programming features that will improve the control for some applications. The CN2120 has the capability of splitting the control output between 2 outputs in the "Split Range" feature. Another program feature allows use with quick opening and equal percentage type valves.
Digital Inputs Three Digital inputs are standard on the CN2120 with options for up to 8 additional inputs. These inputs can be programmed to: • Select between Run/Hold • Abort a program • Select a program • Auto/manual selection • Set output limit • Reset alarm • Reverse or direct control action
Digital Outputs Outputs 2, 3 and 4 can be used as digital outputs. In addition, options are available for 5 or 10 additional outputs. These outputs can be programmed as: • Break event • Timer event • End of cycle annunciator • Program in Run, Hold or Wait State • Controller in manual or auto state • Error annunciation

| T/C Type | Range °C | Range °F | | B PT-30% RH/PT-6% RH | 0 to 1820 | 32 to 3300 | | C 5% RE-W/ 26% RE-W | 0 to 2300 | 32 to 4170 | | D W3-RE/W25-RE | 0 to 2300 | 32 to 4170 | | E CHROMEGA®-CONSTANTAN | -100 to 800 | -150 to 1470 | | G W/W26-RE | 0 to 2300 | 0 to 4170 | | L J DIN | -100 to 900 | -150 to 1650 | | J IRON-CONSTANTAN | -100 to 1000 | -150 to 1830 | | K CHROMEGA®-ALOMEGA® | -100 to 1370 | -150 to 2500 | | N OMEGA-P, OMEGA-N | -100 to 1400 | -150 to 2550 | | Ni/NiMo PT-13% | 0 to 1200 | 32 to 2190 | | R PT-13% RH-PT | -50 to 1760 | -60 to 3200 | | S PT/10% RH-PT | -50 to 1760 | -60 to 3200 | | T COPPER-CONSTANTAN | -200 to 400 | -330 to 750 | | U T DIN | -200 to 600 | -330 to 1110 |
| Model Number | Description | | CN2120-(*)-(*) | Ramp/soak profile controller | | CN2121-(*)-(*) | Ramp/soak profile controller with output failure detection or potentiometer feedback (field selectable) | Outputs 1 and 2 (insert suffix) (Control, Alarm, or Event Assignable) | Suffix | Output 1 | Output 2 | | -R1-R2 | Relay | Relay | | -T1-T1 | ac SSR | ac SSR | | -DC1-R2 | dc Pulse | Relay | | -DC1-DC2 | dc Pulse | dc Pulse | Option | Suffix | Output 5 | Output 6 | | -F5-F6 | 0 to 20, 4 to 20 mA | 0 to 20, 4 to 20 mA | Power Supply Option | Suffix | Discription | | -LV | 24 Vac/Vdc power | Options (only one option available per unit) | Suffix | Discription | | -A2 | RS-485, aux. power supply | | -A4 | RS-485, aux. power supply, clock | | -A6 | RS-485, aux. power supply, 4 logic inputs, 5 digital outputs | | -A7 | RS-485, aux. power supply, 8 logic inputs, 10 digital outputs | | -A8 | RS-485, aux. power supply, 4 logic inputs, 5 digital outputs, clock | | -A9 | RS-485, aux. power supply, 8 logic inputs, 10 digital outputs, clock |
|
| |
 |
|
 |
|
 |
† All dollar amounts on this site are shown in US currency.
Ordering Example: (1) CN2120-DC1-DC2 Ramp/soak profile controller with dc Pulse on output 1 and dc Pulse on output 2, $925.00, plus (1) CN2120-DC1-R2 Ramp/soak profile controller with dc Pulse on output 1 and Relay on output 2, $925.00, plus (1) CN2120-R1-R2 Ramp/soak profile controller with Relay on output 1 and Relay on output 2, $925.00, plus (1) CN2120-T1-T2 Ramp/soak profile controller with ac SSR on output 1 and ac SSR on output 2, $925.00, plus (1) CN2121-DC1-DC2 Ramp/soak profile controller with output fail detection, dc Pulse on output 1 and dc Pulse on output 2, $975.00, plus (1) CN2121-DC1-R2 Ramp/soak profile controller with output fail detection, dc Pulse on output 1 and Relay on output 2, $975.00, $925.00 + 925.00 + 925.00 + 925.00 + 975.00 + 975.00 = $5,650.00
|
|
 |
|
 |
|  |
 |
 |
 |
 |
 |
 |
 |
 |
 |