The Model CSMSTR is a communications and control platform
designed for use with Modular Controller Series slave modules. The
CSMSTR uses a proprietary high speed serial protocol to
communicate, via backplane connection, with up to 16 slave
modules. Through the same connection, the Master also provides
power to the modules.
When powered up, the CSMSTR automatically identifies and
addresses connected slave modules. By storing the configuration
information of all of the modules, the CSMSTR is able to
automatically configure modules if they are replaced.
The Master provides high-speed RS232/422/485 communication
ports and an Ethernet port for connection to PCs, PLCs, and SCADA
systems. An extensive list of master and slave protocol drivers are
available to allow the CSMSTR to share and exchange variable data
with external devices. The 10 Base-T/100 Base-TX Ethernet port can
also be used to connect and share data with other devices at high
speeds. The virtual HMI feature allows you to create and control an
HMI from any networked PC. An onboard CompactFlash slot
provides storage for the Master’s built-in data logger.
The design of the Modular Controller Series high density packaging
and DIN rail mounting saves time and panel space. The controller
snaps easily onto standard top hat (T) profile DIN rail.
The CSMSTR is programmed with Crimson 2.0 software for Windows®
2000 or later platforms. The software is an easy to use, graphical
interface which provides a means of communication configuration,
as well as commissioning and calibration of new systems.
SPECIFICATIONS
Power: 24 Vdc ± 10% 400 mA min. (1 module) 3.5 Amps max. (16 modules + Expansion Card) Must use Class 2 or SELV rated power supply
Communications:
USB/PG Port: Adheres to USB specification 1.1 (Device only using Type B connection)
Serial Ports: Format and Baud Rates for each port are individually software programmable up to 115,200 baud RS232/PG Port: RS232 port via RJ12
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12
DH485 TXEN: Transmit enable; open collector, VOH=15 Vcd, VOL=0.5 V @ 25 mA max
Ethernet Port: 10 BASE-T / 100 BASE-TX RJ45 jack is wired as a NIC (Network Interface Card)
LEDs:
STS: Status LED indicates condition of master
TX/RX: Transmit/Receive LEDs show serial activity
Ethernet: Link and activity LEDs
CF: CompactFlash LED indicates card status and read/write activity
Memory:
On-Board User Memory: 4 MB of non-volatile flash memory
On-Board SDRAM: CSMSTRSX=2MB; CSMSTRGT=8 MB
Memory Card: Compactflash type II slot for type I and type II cards
Real-Time Clock: Typical accuracy is less than one minute per month drift. Crimson 2.0’s SNTP facility allows synchronization with external servers
Battery: Lithium coin cell (included). Typical lifetime of 10 years at 25 ºC (77°F) A "battery low" system variable is available so that the programmer can choose specific action(s) to occur when the battery voltage drops below its nominal voltage.
Environmental Conditions:
Operating Temperature Range: 0 to 50°C (32 to 122°F)
Storage Temperature Range: -30 to +70°C (-22 to 158°F)
Operating and Storage Humidity: 80% max relative humidity, non-condensing, from 0 to 50°C (32 to 122°F)
Vibration According to IEC 68-2-6: 5 to 150 Hz, in X, Y, Z direction for 1.5 hours, 2 g's
Shock According to IEC 68-2-27: Operational 25 g, 11 msec in 3 directions
Altitude: Up to 2000 meters
Construction: Case body is burgundy high impact plastic and stainless steel. Installation category I, pollution degree 2
Power Connection: Removable wire clamp screw terminal block
Wire Gage Capacity: 24 AWG to 12 AWG
Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)
Mounting: Snaps onto standard DIN style top hat (T) profile mounting rails according to EN50022 -35 x 7.5 and -35 x 15
Certifications and Compliances:
Safety: UL Listed, File #E302106, UL508, CSA 22.2 No. 14-M05 Listed by Und. Lab. Inc. to U.S. and Canadian safety standards
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment for measurement, control, and laboratory use, part 1
Electromagnetic Compatability:
Emissions and Immunity to EN 61326: Electrical equipment for measurement, control and laboratory use
Immunity to Industrial Locations*: Electrostatic discharge EN 61000-4-2 Criterion A2; 4 kV contact discharge; 8 kV air discharge; Electromagnetic RF fields EN 61000-4-3 criterion A 10 V/m; Fast transients (burst) EN 61000-4-4 Criterion A; 2 kV power; 2 kV signal; Surge EN 61000-4-5 Criterion A; 1kV L-L,2 kV L&N-E power; RF conducted interference EN 61000-4-6 Criterion A; 3 V/rms
Emissions: Emissions EN 55011 class A
Weight: 456.4 g (15.1 oz)
|
 |
|
 |
† All dollar amounts on this site are shown in US currency.
Note: Comes with termination plug, terminal power block and complete operator’s manual
Ordering Example: (1) CSMSTRSX Controller, (1) SFCRM2MC Software, (1) G3CF512M 512MB flash card, (1) PSDR0100 power supply = $1458
|
|
 |
|
 |
|  |
|
Keywords:Enhanced Modular Controller Series Master
|