Rate/Total/Batch Meters |
| DPF400 |
|
 |
|
|
|
 |
The DPF400 Series is a complete
line of flowrate indicators offering
exceptional performance at an
economical price. Individual models
are available for flowrate and
totalization (with or without square
root extraction) batch control.
The DPF400 is front panel
programmable to scale any input
range to display in desired
engineering units. Independent
scale factors for rate and total allow
rate indication and totalization in
different units, such as GPM rate
and total barrels. If the optional
RS-232 or RS-485 communications
are installed, the unit may also be
programmed by remote computer.
The DPF400 is available with
4 input types, including TTL/open
collector pulse, low level frequency,
analog voltage or analog current.
The unit can be user-configured
for one of three functions:
- a ratemeter/totalizer/batcher
- a ratemeter/totalizer/batcher
with square root extraction
(for differential pressure
flow measurement)
- a batch controller only with
multibatch counting, auto/manual
batch recycle, and remote or
local STOP/CONTINUE control
(START control can be obtained
with a user supplied switch in
series with the control relay)
Options to the DPF400 include
analog and BCD outputs,
alarm/control outputs, and RS-232
or RS-485 communications.
The RS-232 or RS-485
communications options are
bi-directional, allowing the user
to configure the DPF400 as well
as read current values.
While each DPF400 comes
standard with 5 open collector
outputs, the optional DP40-R board
provides dual 7A mechanical relays
which replace two of the open
collector alarms, for a total of
two 7A relay and three open
collector alarms.
SPECIFICATIONS
TTL Level Inputs (DPF401): 0.7 to 2.0 V threshold; 0.2 Hz to 20 kHz frequency; 24 V protection, positive trigger slope; 16 to 30 V unregulated 75 mA sensor excitation
Isolated Pulse Input with Excitation(DPF402): 60 Vrms with protection to 240 V max signal
NPN Open Collector Input (DPF402): 3-wire connection; 12 V regulated excitation
NAMUR Input (DPF402): 2-wire connection; 8.2 V excitation; 1 kohm impedance; <1 mA activated, >3 mA deactivated
Contact Closure Input (DPF402): 2-wire connection; 12 V regulated sensor excitation, 10 on/off per second frequency range
Analog Input (DPF403): 0 to 5 V, 1 to 5 V, or 4 to 20 mA range; 0 to 10 V, or 0 to 1 mA inputs optionally available; 354 Vp isolation; programmable low-level shutoff; 0.02% FS non-linearity; 0.05% FS accuracy; accuracy, 50 ppm/°C temperature coefficient, maximum
Display: 6-digit, 14-segment LED, red or green; 13.8 mm H (0.54"); indicator lights for alarms and status modes
Display Update: 0.04 to 3 seconds, programmable.
Min. Input Frequency: 0.2 Hz
Power: 115 std., 230 Vac opt. 50/60 Hz; 10 Watts maximum
Accuracy: Frequency: 0.01% of reading; Analog: 0.05% of full scale
Step Response: Analog: 50 msec for 10 to 90% FS; Frequency: equal to selected gate time
Operating Ambient Range: 0 to 50°C (32 to 122°F), 95% RH, non-condensing
Storage Temperature: -40 to 85°C (-40 to 185°F)
RS-232 Communications (optional): Front panel programmable for 300/1200/2400/4800/9600/19.2k baud; RJ11 4-wire connection; complete program setup and message display capability; programmable to transmit all measured values, alarm status, actual measured input value (not scaled) and status on programmable intervals from 1 to 60,000 seconds.
RS-485 Communications (optional): 300/1200/2400/4800/9600/19.2k baud; RJ11 6-wire connection; addressable from 0 to 199
Open Collector Outputs: Five 150 mA @ 1 Vdc sink; 30 V open
BCD Output (optional): Isolated; 3- or 6-digit addressing; TTL level output; 5 Vdc external power supply required for isolated output
Mechanical Relays (optional): dual, form C; 7A at 230 Vac/30 Vdc
Analog Outputs (optional): 0 to 5 V/ 1 to 5 V/0 to 10 V/0 to 20 mA/4 to 20 mA all field selectable; all internally powered (sourcing); 600 ohms max. loop impedance for 20 mA outputs; min. 500 ohms input impedance for voltage outputs; 354 Vp isolation; 15-bit resolution; 0.1% of reading accuracy; 50 ms step response; fully adjustable zero and span adjustments.
Dimensions: 48 H x 96 W x 149 mm D (1.89 x 3.78 x 5.86")
Panel Cutout: 45 H x 92 mm W (1.772 x 3.622"); 1⁄8 DIN
Weight: 574 g (1.27 lb)
|
| |
 |
|
 |
|
 |
† All dollar amounts on this site are shown in US currency.
Note: DP40-B and DP40-R cannot both be installed in one unit.
Ordering Example: (1) DPF403-GR 4-20 mA/0-5 Vdc/1-5 Vdc (field-selectable) input meter with green display, $590.00
|
|
 |
 |
 |
 |
 |
 |
 |
|
 |
 |
Part Number Builder |
 |
 |
 |
 |
 |
 |
|
|
|
Option Descriptions
|
|
(1)
|
|
| |
Select DPF401 for TTL/Open Collector/Contact Closure Input Meter DPF402 for Low Level Pulse Input Meter DPF403 for 4-20 mA/0-5 Vdc/1-5 Vdc (field-selectable) Input Meter
|
(2)
|
Power Options
|
| |
Select for 115 Vac leave blank -230V for 230 Vac power
|
(3)
|
Display Color
|
| |
Select for red display leave blank -GR for green display
|
|
NOTE: All combinations may not be valid, check spec sheet for valid part numbers.
|
| |
|
 |
|
|
 |
|  |
 |
 |
 |
 |
 |
 |
 |
 |
 |