OMEGAPHONE Alarm Dialer Four Temperature Channels Plus Four Powered Inputs with Optional Ethernet Data Collection |
| OMA-VM540 and OMA-VM541 |
|
 |
|
|
|
|
|
|
|
| |
Monitors The Temperature of Up to Four Individual Areas and Up To Four Powered Inputs
|
| |
Monitors One Dry Contact (Switch Closure) Input
|
| |
Programmable High and Low Temperature Limits and Alarm Time Delay for Each Room
|
| |
Programmable “Normal” Power State and Alarm Time Delay for Each Power Input
|
| |
Programmable Alarm Time Delay for Auxiliary Dry Contact Input
|
| |
Calls up to Four Programmable Phone Numbers
|
| |
Call and Hear the Temperature, Power, or Input Status Any Time
|
| |
Pager Compatible Leaves Call Back Number on Numeric Pagers
|
| |
Programmed Settings are Never Lost!
|
| |
Recordable Greeting Message and Input Identification Messages for Each Input
|
| |
Rechargeable Backup Battery (Included)
|
View related products - Auto-Dialers and Alarm Monitoring Systems
|
| |
|
|
|
 |
The OMA-VM540 monitors the temperature of up to four areas
and up to four 12 Vdc powered inputs. The OMA-VM541 monitors
the temperature of up to four areas and up to four 24 Vac powered
inputs. The OMA-VM540 and OMA-VM541 will call and alert you
with a voice message or a pager alert when a temperature is out of
limits and your valuable equipment is in danger of being damaged.
The OMA-VM540 and OMA-VM541 will call you if power is lost at any
input or the auxiliary alarm input becomes active.
Remote Status Checking
The OMA-VM540 and OMA-VM541 can be called at any time to check
the status of any input.
Emergency Phone Calls
When a temperature input is out of programmed limits, a
power input changes from its normal state, the power at the
wall-mount power adapter is out, or a contact closure occurs on
the auxiliary dry contact input the OMA-VM540 and OMA-VM541 will
dial all programmed phone numbers until contact is made. If contact has
not been made after dialing all phone numbers, the OMA-VM540
and OMA-VM541 will wait twenty minutes and then begin calling
again.
This sequence is repeated until contact is made. When the
OMA-VM540 and OMA-VM541 is calling a standard voice number,
it will play the recorded alarm message and the current alarm
condition. The OMA-VM540 and OMA-VM541 will then prompt the
user to enter the PIN. When the correct PIN is entered, contact has
been made.
The OMA-VM540 and OMA-VM541 will stop calling until a new alarm
condition occurs. When the OMA-VM540 and OMA-VM541
calls a pager number, it will transmit the programmable Local ID Number
for display on the pager screen.
Ethernet Data Collection
The optional Ethernet data collection package allows you
to remotely check the dialer status with a standard web browser.
Using this package you can view real time data, view historical data,
automatically send alarm emails to key personnel that specify the
exact location and cause of the problem, maintain secure data
files, easily create and print graphs over specified time periods for
any data and also program temperature limits and power
input parameters remotely.
General Specifications
Telephone: Standard RJ11 phone jack connector
Telephone Numbers: Stores up to four phone numbers
up to 20 digits long
Recording Time for the Local Identification Message:
5 seconds
Recording Time for Individual Channel Identification
Mesages: 2 seconds
Alarm Notification: Alarm siren sounds and alarm relay
closes if any temperature input goes out of limits, a powered input changes
state, or the auxillary alarm input becomes active.
Alarm Cancellation: Pushbutton on front of the unit silences the
alarm and cancels the emergency telephone calls.
Display: Integral LCD display
Power Requirements: 120 Vac at 50/60 Hz wall mount
transformer (included)
Battery Backup: 4-hour rechargeable battery backup;
20-hour or 30-hour optional
Electrical Connections: Pluggable 12 position terminal blocks
Ambient Operating Conditions: 0 to 51°C (32 to 125°F)
Material: ABS plastic
Dimensions:
117 H x 223 W x 57 mm D
(4.62 x 8.79 x 2.26")
Weight: 0.9 kg (2 lbs)
Specifications
OMA-VM540
Temperature Inputs: 4
Temperature Measuring Range: -40 to 212°C (-40 to 100°F)
Temperature Sensor Type: 2-wire 1000 Ω Pt RTD, α =.00385
Accuracy: ±1°C (2°F)
Resolution: 1°C (1°F)
Powered Inputs: 4
Powered Input Range: 12 Vdc
OUTPUTS:
Relay: 30 V dc 1A contacts
Alarm Buzzer: 85 dB
OMA-VM541
Temperature Inputs: 4
Temperature Measuring Range:
-200 to 200°C (-328 to 392°F),
Accuracy: ±1°C (2°F)
Resolution: 1°C (1°F)
Temperature Sensor Type:
2-wire 100 Ω Pt RTD, α = 00385
Powered Inputs: 4
Powered Input Range: 24 Vac
OUTPUTS:
Relay: 30 Vdc 0.5A contacts
Alarm Buzzer: 85 dB
Ethernet Data Collection
LAN: Ethernet 10Base-T or 100Base-TX (auto-sensing)
Transport Protocol: TCP/IP, UDP
Connector: RJ45
LED Indicators: 10Base-T connection, 100Base-TX
connection, link and activity indicator (full/half duplex)
|
| |
 |
|
 |
|
 |
† All dollar amounts on this site are shown in US currency.
Note: Each unit is supplied with complete user’s manual and ac adaptor.
|
|
 |
|
 |
|  |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Related Links -
Related Products
|
 |
 |
 |
 |
 |
 |
|
Related Products
|
 |
RTD-(*)-F3105:
|
|
RTD Elements with 36 Inch Lead Wire form 2, 3 or 4 Wire RTD Sensor Probe
|
 |
 |
|
|
|
 |
 |
|
|