Anemometer with Real-Time Data Logger |
| HHF2005 |
|
 |
|
|
Anemometer with Real-Time Data Logger
 |
| Click for larger image. |
|
|
$
539.00
HHF2005
|
| |
Real Time Data Logger Records Year, Month, Date, Hour, Minute and Second—Up to 16,000 Records
|
| |
Heavy Duty Metal Van Gives Very Accurate Low and High Velocity Air Measurements
|
| |
Battery Powered Meter Includes Hard Carrying Case For Easy Portability
|
| |
Jumbo LCD With Multiple Displays Can be Adjusted For Brightness
|
| |
Adjustable Sampling Time and Data Hold Features
|
| |
Accepts Type J or K Thermocouple
|
View related products - Air Velocity Indicators & Wind Tunnels
|
| |
|
|
|
 |
The HHF2005 anemometer with
real time data logger has multiple
features and an RS232 computer
interface that make it suitable to
use in a variety of HVAC
applications, such as environmental
testing, flow hoods and wind speed
measurements. What sets the
HHF2005 apart from other
anemometers is that it incorporates a real-time data logger that can
store up to 16,000 entries. The
HHF2005 measures velocity and air
temperature, and has an input
probe socket that accepts a Type J
or K thermocouple that can be used
as a highly accurate thermometer.
By entering the area into the
instrument and measuring the
velocity, the HHF2005 can even determine the volume of air flow.
The integrated thermistor provides
fast and accurate readings - at low
or high velocities. For added
convenience, the HHF2005 is
battery powered, has auto power
off and low battery warning
features. A hard carrying case is
included to make portability simple.
SPECIFICATIONS
Display Units: m/s, km/h, mile/h, knot, ft/min, CMM, CFM, °C, °F
Operating Temperature: 0 to 50°C (32 to 122°F)
Max Humidity: Less than 80% relative humidity (non-condensing)
Sampling Time: 2 sec to 8 hours, 59 min, 59 sec
Power Supply: 4 "AA" batteries (included)
Current: Approx 21.5 mA DC (27.5 mA DC with vane)
Weight: Approx 515 g (1.13 lb)
Dimensions:
Instrument: 203 x 76 x 38 mm (8.0 x 3.0 x 1.5")
Metal Vane: 72 mm (2.8") dia
LCD Display: 58 x 34 mm (2.3 x 1.3")
| Measurement | Range | Resolution | Accuracy |
| m/s | 0.4 to 30.0 m/s | 0.1 m/s | ± (2% + 0.2 m/s) |
| km/hr | 1.4 to 108.0 km/hr | 0.1 km/hr | ± (2% + 0.8 km/hr) |
| mile/hr | 0.9 to 67.0 mile/hr | 0.1 mile/hr | ± (2% + 0.4 mile/hr) |
| knot | 0.8 to 58.3 knot | 0.1 knots | ± (2% + 0.4 knot) |
| ft/min | 80 to 5910 ft/min | 1 ft/min | ± (2% + 40 ft/min) |
| Air temp (°C) | 0 to 50°C | 0.1°C | ± 0.8°C |
| Air temp (°F) | 32 to 122°F | 0.1°F | ± 1.5°F |
Type J thermocouple Thermometer | -100.0 to 1100°C | 0.1°C | ± (0.2% + 0.5°C) |
| -50.1 to -100°C | ± (0.2% + 1°C) |
| -58.0 to 2012°F | 0.1°F | ± (0. 2% + 1°F) |
| -58.1 to -148°F | ± (0.2% + 1.8°F) |
Type K thermocouple Thermometer | -50.0 to 1300°C | 0.1°C | ± (0.2% + 0.5°C) |
| -50.1 to -100°C | ± (0.2% + 1°C) |
| -58.0 to 2372°F | 0.1°F | ± (0.2% + 1°F) |
| -58.1 to -148°F | ± (0.2% + 1.8°F) |
| Measurement | Range | Resolution | Area |
| CMM | 0 to 54,000 CMM | 0.001-1 CMM | 0.001 to 30.0 m2 |
| CFM | 0 to 1,908,300 CFM | 0.01-100 CFM | 0.01 to 322.91 ft2 |
|
| |
 |
|
 |
|
 |
† All dollar amounts on this site are shown in US currency.
Note: Comes complete with operator's manual, 1 CR2032 battery, 4 "AA" batteries, hard carrying case and batteries.
Ordering Example: (1) HHF2005 Vane anemometer with data logger, $539
|
|
 |
|
 |
|  |
|
Back to top
|
|